Unit Setup Parameters
Unit Setup Parameters
UPS SETUP PARAMETERS
VERSION 03.33
AC VOLTS PROTECTIONS FREQUENCY I LIMIT MAX POWER
OUTPUT 208 +10%, -10% 60 HZ +/-1.00 HZ 280. AMPS 80. KVA
RECTIFIER 480 +11%, -20% 60 HZ +/-3.00 HZ 131. AMPS
BYPASS 480 +10%, -10% 60 HZ +/-0.50 HZ
INVERTER 228 +15%, -10% 60 HZ +/-1.00 HZ
---- CURRENT LIMITS ----
OUTPUT OUTPUT RECTIFIER
100% OVERLOAD ON GENERATOR
222.0 229.0 105.0
---- PHASE OFFSETS ----
BYPASS OUTPUT
25 80
INVERTER TO OUTPUT TRANSFORMER RATIO ----- 0.910
DC LINK
NOMINAL BATTERY BATTERY VDC PROTECTION BATTERY BATTERY
VDC VDC EQUALIZE DCUV DCOV I LIMIT I 100%
540 480 540 400 620 +32. AMPS -160 AMPS
---- BATTERY DATA ----
POINT 1 2 3 4 5 6 7
BATTERY KW LOAD 10.0 30.0 39.0 66.0 78.0 98.0 122.0
MINIMUM BATTERY VOLTS 415.0 400.0 400.0 400.0 400.0 400.0 400.0
BATTERY TIME (MINUTES) 240 60 40 20 15 10 7
AH MINIMUM # OF BATTERIES MAXIMUM BATTERY
RATING VOLTS BANKS PER BANK BAT EFF EQUALIZE COUNT
225.0 400.0 3 40 98% 8
DC LINKS ARE NOT IN PARALLEL
UPS OUTPUTS ARE NOT IN PARALLEL
UNIT DOESN'T HAVE AN AUTOMATIC RECTIFIER INPUT BREAKER
UNIT DOESN'T HAVE AN AUTOMATIC BYPASS BREAKER
BATTERY TIME REMAINING DISPLAY IS ENABLED
CSA OPTION IS NOT INSTALLED
AUTO RESTART IS ENABLED
AUTO BATTERY EQUALIZING IS DISABLED
AUTOMATIC INTERNAL DISPLAY BLANKING IS ENABLED
PARALLEL TIME IS 0.64 SECONDS
---- BUILDING ALARMS ----
REMOTE GOTO BYPASS IS ENABLED
BUILDING ALARM 6 REPORTING IS ENABLED
BUILDING ALARM 5 REPORTING IS ENABLED
BUILDING ALARM 4 REPORTING IS ENABLED
BUILDING ALARM 3 REPORTING IS ENABLED
BUILDING ALARM 2 REPORTING IS ENABLED
BUILDING ALARM 1 REPORTING IS ENABLED
---- COMMUNICATIONS BOARD PORT ASSIGNMENTS ----
UNIT KEYBOARD/DISPLAY -- FRONT PANEL CONTROLLED DISPLAY
RS232#1 (COM) -- FRONT PANEL CONTROLLED PRINTER, ANSI TERMINAL
BAUD RATE 19200, 8 BITS, 1 STOP BIT, NO PARITY
HARDWARE HANDSHAKING IS DISABLED
RS232#2 (COM) -- FRONT PANEL CONTROLLED PRINTER, ANSI TERMINAL
BAUD RATE 19200, 8 BITS, 1 STOP BIT, NO PARITY
HARDWARE HANDSHAKING IS DISABLED
OPERATING POINTS/SCALE FACTORS
RECTIFIER CURRENT LIMIT OPERATING POINT ---------------- 58362
RECTIFIER ON GENERATOR CURRENT LIMIT OPERATING POINT --- 46778
RECTIFIER CURRENT METER SCALE FACTOR ------------------- 2998
RECTIFIER KW METER SCALE FACTOR ------------------------ 8964
RECTIFIER CURRENT BAR CHART SCALE FACTOR --------------- 46319
OPERATING POINT FOR 126% OUTPUT CURRENT ---------------- 56155
OUTPUT 100% CURRENT LIMIT OPERATING POINT -------------- 44523
OUTPUT OVERLOAD CURRENT LIMIT OPERATING POINT ---------- 45927
OUTPUT CURRENT METER SCALE FACTOR ---------------------- 5986
OUTPUT KW METER SCALE FACTOR --------------------------- 4531
OUTPUT CURRENT BAR CHART SCALE FACTOR ------------------ 24275
INVERTER VOLTAGE OPERATING POINT ----------------------- 46089
OUTPUT VOLTAGE OPERATING POINT ------------------------- 19053
BATTERY CHARGE CURRENT OPERATING POINT ----------------- 33228
BATTERY CURRENT BAR CHART SCALE FACTOR ----------------- 4110
NOMINAL DC VOLTAGE OPERATING POINT --------------------- 35591
DC VOLTS BAR CHART SCALE FACTOR ------------------------ 15716
Main
*
Alarm/Event Queue
*
Unit Setup Parameters
*
Active Alarms
*
Meter Values
This page last updated: Friday, July 13, 2018 at 5:56PM