Unit Setup Parameters

Unit Setup Parameters


                              UPS SETUP PARAMETERS
                                 VERSION 03.33

               AC VOLTS  PROTECTIONS     FREQUENCY      I LIMIT   MAX POWER
     OUTPUT      208     +10%, -10%  60 HZ  +/-1.00 HZ 280. AMPS   80. KVA
     RECTIFIER   480     +11%, -20%  60 HZ  +/-3.00 HZ 131. AMPS   
     BYPASS      480     +10%, -10%  60 HZ  +/-0.50 HZ 
     INVERTER    228     +15%, -10%  60 HZ  +/-1.00 HZ 

                            ---- CURRENT LIMITS ----
                         OUTPUT    OUTPUT    RECTIFIER
                          100%    OVERLOAD  ON GENERATOR
                          222.0     229.0      105.0

                            ---- PHASE OFFSETS ----
                                BYPASS  OUTPUT
                                   	25    	80

          INVERTER TO OUTPUT TRANSFORMER RATIO ----- 0.910

                              DC LINK

        NOMINAL   BATTERY   BATTERY VDC   PROTECTION   BATTERY    BATTERY
          VDC       VDC      EQUALIZE     DCUV  DCOV   I LIMIT    I 100%
          540       480         540        400   620  +32. AMPS  -160 AMPS

                             ---- BATTERY DATA ----

                POINT     1      2      3      4      5      6      7
BATTERY KW LOAD          10.0   30.0   39.0   66.0   78.0   98.0  122.0 
MINIMUM BATTERY VOLTS   415.0  400.0  400.0  400.0  400.0  400.0  400.0 
BATTERY TIME (MINUTES)    240     60     40     20     15     10      7 

          AH     MINIMUM    # OF   BATTERIES   MAXIMUM      BATTERY
        RATING    VOLTS    BANKS   PER BANK    BAT EFF   EQUALIZE COUNT
         225.0     400.0       3        40         98%            8

      DC LINKS ARE NOT IN PARALLEL
      UPS OUTPUTS ARE NOT IN PARALLEL
      UNIT DOESN'T HAVE AN AUTOMATIC RECTIFIER INPUT BREAKER
      UNIT DOESN'T HAVE AN AUTOMATIC BYPASS BREAKER
      BATTERY TIME REMAINING DISPLAY IS ENABLED
      CSA OPTION IS NOT INSTALLED
      AUTO RESTART IS ENABLED
      AUTO BATTERY EQUALIZING IS DISABLED
      AUTOMATIC INTERNAL DISPLAY BLANKING IS ENABLED
      PARALLEL TIME IS 0.64 SECONDS

                           ---- BUILDING ALARMS ----

                     REMOTE GOTO BYPASS IS ENABLED
                     BUILDING ALARM 6 REPORTING IS ENABLED
                     BUILDING ALARM 5 REPORTING IS ENABLED
                     BUILDING ALARM 4 REPORTING IS ENABLED
                     BUILDING ALARM 3 REPORTING IS ENABLED
                     BUILDING ALARM 2 REPORTING IS ENABLED
                     BUILDING ALARM 1 REPORTING IS ENABLED

                ---- COMMUNICATIONS BOARD PORT ASSIGNMENTS ----

            UNIT KEYBOARD/DISPLAY -- FRONT PANEL CONTROLLED DISPLAY
            RS232#1 (COM) -- FRONT PANEL CONTROLLED PRINTER, ANSI TERMINAL
                 BAUD RATE 19200, 8 BITS, 1 STOP BIT, NO PARITY
                 HARDWARE HANDSHAKING  IS DISABLED
            RS232#2 (COM) -- FRONT PANEL CONTROLLED PRINTER, ANSI TERMINAL
                 BAUD RATE 19200, 8 BITS, 1 STOP BIT, NO PARITY
                 HARDWARE HANDSHAKING  IS DISABLED

                         OPERATING POINTS/SCALE FACTORS

     RECTIFIER CURRENT LIMIT OPERATING POINT ---------------- 58362
     RECTIFIER ON GENERATOR CURRENT LIMIT OPERATING POINT --- 46778
     RECTIFIER CURRENT METER SCALE FACTOR -------------------  2998
     RECTIFIER KW METER SCALE FACTOR ------------------------  8964
     RECTIFIER CURRENT BAR CHART SCALE FACTOR --------------- 46319
     OPERATING POINT FOR 126% OUTPUT CURRENT ---------------- 56155
     OUTPUT 100% CURRENT LIMIT OPERATING POINT -------------- 44523
     OUTPUT OVERLOAD CURRENT LIMIT OPERATING POINT ---------- 45927
     OUTPUT CURRENT METER SCALE FACTOR ----------------------  5986
     OUTPUT KW METER SCALE FACTOR ---------------------------  4531
     OUTPUT CURRENT BAR CHART SCALE FACTOR ------------------ 24275
     INVERTER VOLTAGE OPERATING POINT ----------------------- 46089
     OUTPUT VOLTAGE OPERATING POINT ------------------------- 19053
     BATTERY CHARGE CURRENT OPERATING POINT ----------------- 33228
     BATTERY CURRENT BAR CHART SCALE FACTOR -----------------  4110
     NOMINAL DC VOLTAGE OPERATING POINT --------------------- 35591
     DC VOLTS BAR CHART SCALE FACTOR ------------------------ 15716